8.8 Jogging
Overview
The "Jog" function is typically used to temporarily move a motor using local control commands.
Requirement
The OFF1 command must be active. With an active ON command, the converter ignores the
commands "Jogging 1" and "Jogging 2".
Function description
5HDG\WRVZLWFKRQ
2SHUDWLRQ
QRMRJJLQJ-RJJLQJ
Commands "Jog 1" or "Jog 2" switch the motor on and o󹪜.
The commands are only active when the converter is in the "Ready for switching on" state.
0RWRUVSHHG
0D[LPXPVSHHG
-RJJLQJ
6HWSRLQWMRJJLQJ
6HWSRLQWMRJJLQJ
-RJJLQJ
S
S
S
W
W
W
SS
Figure 8-21 Behavior of the motor when "jogging"
After switching on, the motor accelerates to the setpoint, jog 1 or setpoint, jog 2. The two
di󹪜erent setpoints can, for example, be assigned to motor clockwise and counter-clockwise
rotation.
When jogging, the same ramp-function generator is active as for the ON/OFF1 command.
Example
Parameter Description
p1055 = 722.0 Jogging bit 0: Select jogging 1 via digital input 0
p1056 = 722.1 Jogging bit 1: Select jogging 2 via digital input 1
Advanced commissioning
8.8 Jogging
Distributed converter for SIMOGEAR geared motors
218 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL