Example
To switch on the motor using digital input DI 2, you must connect the status parameter of DI 2
with p0840: Set p0840 = 722.2
Parameter
Table 8-3 Binector inputs (BI) of the converter (selection)
BI Meaning BI Meaning
p0810 Command data set selection CDS bit 0 p1036 Motorized potentiometer setpoint lower
p0840 ON/OFF1 p1055 Jogging bit 0
p0844 OFF2 p1056 Jogging bit 1
p0848 OFF3 p1113 Setpoint inversion
p0852 Enable operation p1201 Flying restart enable signal source
p0855 Unconditionally open holding brake p2103 1. Acknowledge faults
p0856 Enable speed controller p2106 External fault 1
p0858 Unconditionally close holding brake p2112 External alarm 1
p1020 Fixed speed setpoint selection, bit 0 p2200 Technology controller enable
p1021 Fixed speed setpoint selection, bit 1 p3330 2-3-WIRE control command 1
p1022 Fixed speed setpoint selection, bit 2 p3331 2-3-WIRE control command 2
p1023 Fixed speed setpoint selection, bit 3 p3332 2-3-WIRE control command 3
p1035 Motorized potentiometer setpoint higher
A complete list of the binector inputs is provided in the List Manual.
Further information
You can debounce the digital input signal using parameter p0724.
Additional information is provided in the parameter list and function diagrams 2210 .