To make the setting process easier, the converter has various prede󹪝ned assignments (macros).
Only the inputs and outputs whose functions change by selecting a speci󹪝c assignment, are
shown on the following pages.
Procedure
1. Think about which of the input and output functions you are using in the application.
2. Find the I/O con󹪝guration (macro) that best suits your application.
3. Note the macro number of the corresponding default setting.
You must set this macro number when putting the frequency converter into operation.
You have found the appropriate converter pre-assignment.
4.3.10 Wiring example for the factory settings
To ensure that the factory setting of the interfaces can be used, you must wire your drive as
shown in the following examples.
Factory pre-assignment of the interfaces on the drive
For a complete technical speci󹪝cation of the individual connections, please refer to following
section of this manual:
Connection and cables (Page 67)
$FNQRZOHGJHIDXOW
212))
5HYHUVH
$ODUP
)DXOW
6ZLWFKRYHUVRXUFHRIVSHHGVHWSRLQW
6SHHG
VHWSRLQW
)L[HGVSHHGVHWSRLQW
6HWSRLQWIURPWKH3RWHQWLRPHWHU
',
',
',
;
;
;
'2
'2
',
',
',
Figure 4-16 Macro 29 - Conveyer with potentiometer and 󹪝xed setpoint (Default USS)
Installation
4.3 Electrical Installation
Distributed converter for SIMOGEAR geared motors
80 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL