Additional measures
Finely stranded, braided copper cables have to be routed in parallel with the cable shields in the
following cases:
Old installations with already existing unscreened cables
Cables with poor high-frequency properties
Installations with bad grounding systems
The connections in the following 󹪝gure provide a solid, high-frequency bonding between the
driven machine and the converter.
)LQHO\VWUDQGHGEUDLGHG
FRSSHUFDEOH
'ULYHQPDFKLQH
3(
/
/
/
Figure 4-10 Additional high-frequency bonding of the drive system
4.3.3 Protective conductor
WARNING
Danger to life caused by high leakage currents for an interrupted protective conductor
The drive components conduct a high leakage current via the protective conductor. Touching
conductive parts when the protective conductor is interrupted can result in death or serious
injury.
Dimension the protective conductor as stipulated in the appropriate regulations.
Installation
4.3 Electrical Installation
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 65