If you use an input as a failsafe input, set the debounce time as described above.
8.15.2.5 Setting the signal 󹪝lter for STO selection
Overview
If required, you must set the signal 󹪝lter for selecting the STO safety function.
Requirement
You are online with Startdrive.
Function description
Procedure
1. Navigate to the 󹪝lter settings.
2. Set the debounce time for the F-DI input 󹪝lter.
3. Set the discrepancy time for the simultaneity monitoring.
You have set the signal 󹪝lter of the failsafe digital input.
Parameter
Parameter Description Factory setting
p9650 SI F-DI switchover discrepancy time (CPU 1) 500 ms
p9651 SI STO debounce time (processor 1) 1 ms
8.15.2.6 Forced checking procedure
Overview
The forced checking procedure (test stop) is a converter self test, which is necessary when you
have enabled at least one safety function.
Advanced commissioning
8.15 Safe Torque O󹪜 (STO) safety function
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 251