8.7 Control via AS-i
8.7.1 Single slave mode
In Single Slave mode, four bits are available for the communication between the AS-i master and
the converter. The four bits are used to transfer process data. In parallel, the control can start a
diagnostic request via AS-i.P0.
The following default settings are available; both work with pro󹪝le 7.F.E.
Default setting 30: Standard Single Slave mode
Default setting 32: Modi󹪝ed Single Slave mode
Default setting 30: Standard Single Slave mode
In standard addressing, the control speci󹪝es the speed setpoint via the motor control bits (AS-
i.DO0 … AS-i.DO3).
Control -> converter
AS-i.DO0 -> p1020 = 2093.0 Fixed speed bit 0
AS-i.DO1 -> p1021 = 2093.1 Fixed speed bit 1
AS-i.DO2 -> p1022 = 2093.2 Fixed speed bit 2
AS-i.DO3 -> p1023 = 2093.3 Fixed speed bit 3
AS-i System Interface Manual (https://support.industry.siemens.com/cs/gb/en/view/
1171856).
Converter -> control
If the control speci󹪝es the speed setpoint, the converter replies:
p2080[0] = 53.13 -> AS-i.DI0 Operational enable for PLC
p2080[1] = 899.11 -> AS-i.DI1 Pulses enabled
p2080[2] = 722.0 -> AS-i.DI2 State DI0
p2080[3] = 722.1 -> AS-i.DI3 State DI1
If the control sends a diagnostic request via AS-i.P0, the converter replies with the currently
pending fault or alarm messages.
AS-i System Interface Manual (https://support.industry.siemens.com/cs/gb/en/view/
1171856).
Default setting 32: Modi󹪝ed Single Slave mode
In Single Slave mode with modi󹪝ed addressing the control speci󹪝es the following:
Advanced commissioning
8.7 Control via AS-i
Distributed converter for SIMOGEAR geared motors
208 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL