9.7 List of alarms and faults
Axxxxx Alarm
Fyyyyy: Fault
Table 9-11 The most important alarms and faults
Number Cause Remedy
F01000 Software fault in CU Replace CU.
F01001 Floating Point Exception Switch CU o and on again.
F01015 Software fault in CU Upgrade rmware or contact technical support.
F01018 Power-up aborted more than once
1. Switch the module o and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the converter.
A01028 Conguration error Explanation: Parameterization on the memory card has been created with a
dierent type of module (article number, MLFB)
Check the module parameters and recommission if necessary.
F01033 Unit switchover: Reference parame‐
ter value invalid
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
F01034 Unit switchover: Calculation of the
parameter values after reference
value change unsuccessful
Select the value of the reference parameter so that the parameters involved
can be calculated in the per unit notation (p0304, p0305, p0310, p0596,
p2000, p2001, p2002, p2003, r2004).
F01040 Parameters must be saved Save parameters (p0971).
Switch CU o and on again.
F01044 Loading of memory data card defec‐
tive
Replace memory card or CU.
F01105 CU: Insucient memory Reduce number of data records.
A01101 Memory card not available Insert a memory card or disable the warning A01101.
Message for a memory card that is not inserted (Page 140)
F01122 Frequency at the probe input too
high
Reduce the frequency of the pulses at the probe input.
F01205 CU: Time slice overow Contact technical support.
F01250 CU hardware fault Replace CU.
F01512 An attempt has been made to estab‐
lish an conversion factor for scaling
which is not present
Create scaling or check transfer value.
A01590 Motor maintenance interval lapsed Carry out maintenance and reset the maintenance interval (p0651).
F01662 CU hardware fault Switch CU o and on again, upgrade rmware, or contact technical support.
A01900 PROFIBUS: Conguration telegram
faulty
Explanation: A PROFIBUS master is attempting to establish a connection
with a faulty conguration telegram.
Check the bus conguration on the master and slave side.
Alarms, faults and system messages
9.7 List of alarms and faults
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 357