When required, you can use the analog inputs as additional digital inputs.
NOTICE
Defective analog input due to overcurrent
If the analog input switch is set to "Current input" (I), a 10 V or 24 V voltage source results in an
overcurrent at the analog input. An overcurrent condition destroys the analog input.
If you use an analog input as a digital input, then you must set the analog input switch to
"Voltage" (U).
8.4.3 Digital outputs
Function description
2
5
4
1 3
p0730
BO: ryyxx.n
p0731
;
'2
'2
Interconnect the digital output with a binector output of your choice.
Interconnecting signals in the converter (Page 408)
Binector outputs are designated in the parameter list with "BO".
Example
;
2
5
4
1 3
r0052.352.3
S
'2
To output the fault message via digital output DO 1, you must connect DO 1 with the fault
message: Set p0731 = 52.3.
Advanced commissioning
8.4 Adapt the default setting of the inputs and outputs
Distributed converter for SIMOGEAR geared motors
164 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL