4.4.3.2 What do you have to set for communication via PROFIBUS?
Conguring PROFIBUS communication
You require the appropriate engineering system to congure PROFIBUS communication in the
PROFIBUS master.
If required, load the GSD le of the converter into the engineering system.
Installing the GSD (Page 92)
Setting the address
Set the address of the PROFIBUS slave.
Set the PROFIBUS address (Page 93)
Setting the telegram
Set the same telegram in the converter as in the PROFIBUS master. Interconnect the telegrams
in the control program of the PROFIBUS master with the signals of your choosing.
Integrating the converter in PROFIBUS (Page 91)
Application examples
You can nd application examples for PROFIBUS communication on the Internet:
Controlling the speed of a SINAMICS G110M/G120/G120C/G120D with S7-300/400F via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI (https://
support.industry.siemens.com/cs/ww/en/view/60441457)
Controlling the speed of a SINAMICS G110M / G120 (Startdrive) with S7-1500 (TO) via
PROFINET or PROFIBUS, with Safety Integrated (via terminal) and HMI (https://
support.industry.siemens.com/cs/ww/en/view/78788716)
4.4.3.3 Installing the GSD
Procedure
1. Save the GSD on your PC using one of the following methods.
– With Internet access:
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
– Without Internet access:
Insert a memory card into the converter.
Set p0804 = 12.
The converter writes the GSD as zipped le (*.zip) into directory /SIEMENS/SINAMICS/
DATA/CFG on the memory card.
2. Unzip the GSD le on your computer.
3. Import the GSD in the engineering system of the controller.
Installation
4.4 Connecting the converter to the eldbus
Distributed converter for SIMOGEAR geared motors
92 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL