A.1.2 Firmware version 4.7 SP10
Table A-2 New functions and function changes in 󹪝rmware 4.7 SP10
Function SINAMICS
G120 G120D
*0
*&
&83
&8%
&8(
&86
&8'
&8'
(7SUR)&
1 New parameter r7844 [1] for displaying the 󹪝rmware version in plain text.
"04070901" is equivalent to 󹪝rmware version V4.7 SP9 HF1, for example
2 Modbus RTU:
The factory setting of parameter p2040 was increased to provide more
robust converter operation. Monitoring time for data failure at the Mod‐
bus interface: p2040 = 10 s
r2057 indicates how the address switch on the converter is set
- - -
3 BACnet MS/TP:
New factory setting for more robust converter operation:
Baud rate p2020 = 38.4 kBd
Monitoring time for data failure at the BACnet interface was in‐
creased: p2040 = 10 s
Factory setting for the maximum number of info frames p2025 [1] = 5
Factory setting for the maximum number of master addresses p2025
[3] = 32
r2057 indicates how the address switch on the converter is set
- - - - - - - -
4 Further technological unit kg/cm² for unit switchover
5 Further technological unit kg/cm² for additional technology controllers - - - - - - - -
Appendix
A.1 New and extended functions
Distributed converter for SIMOGEAR geared motors
398 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL