1. Open the control panel.
2. Assume master control for the converter.
3. Set the "Drive enables"
4. Switch on the motor.
The converter starts the motor data identi󹪝cation. This measurement can take several
minutes.
Depending on the setting, after motor data identi󹪝cation has been completed, the converter
switches o󹪜 the motor - or it accelerates it to the currently set setpoint.
5. If required, switch o󹪜 the motor.
6. Relinquish the master control after the motor data identi󹪝cation.
7. Save the settings in the converter (RAM → EEPROM):
You have completed the motor data identi󹪝cation.
Self-optimization of the speed control
If you have not only selected motor data identi󹪝cation with the motor stationary, but also
rotating measurement with self-optimization of the speed control, you must switch on the
motor again as described above and wait for the optimization run to 󹪝nish.
Quick commissioning has been completed once the motor data identi󹪝cation has been
successfully completed.
Commissioning
5.4 Quick commissioning
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 129