1. Open the control panel.
2. Assume master control for the converter.
3. Set the "Drive enables"
4. Switch on the motor.
The converter starts the motor data identication. This measurement can take several
minutes.
Depending on the setting, after motor data identication has been completed, the converter
switches o the motor - or it accelerates it to the currently set setpoint.
5. If required, switch o the motor.
6. Relinquish the master control after the motor data identication.
7. Save the settings in the converter (RAM → EEPROM):
You have completed the motor data identication.
❒
Self-optimization of the speed control
If you have not only selected motor data identication with the motor stationary, but also
rotating measurement with self-optimization of the speed control, you must switch on the
motor again as described above and wait for the optimization run to nish.
Quick commissioning has been completed once the motor data identication has been
successfully completed.
Commissioning
5.4 Quick commissioning
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 129