Table 8-2 Commands for switching the motor on and o
ON
Jogging 1
Jogging 2
Enable operation
The inverter switches the motor on.
OFF1, OFF3 The inverter brakes the motor. The inverter switches o the motor once it comes to a standstill.
The motor is considered to be stationary if the speed is less than a dened minimum speed.
OFF2
Inhibit operation
The inverter switches o the motor immediately without rst braking it.
Parameter
Parameter Description Setting
p1226 Standstill detection, speed
threshold [rpm]
Factory setting: 20.00
rpm
The inverter identies that the motor is at a
standstill after OFF1 or OFF3 when at least one
of the following conditions has been satised:
• The speed actual value falls below the thresh‐
old in p1226 and the time started in p1228
has expired.
• The speed setpoint falls below the threshold
in p1226, and the time subsequently started
in p1227 has expired.
p1227 Standstill detection monitor‐
ing time [s]
Factory setting: 300.00 s
p1228 Pulse cancellation delay time
[s]
Factory setting: 0.01 s
Further information
You will nd additional information in function diagram 2610 of the List Manual.
Advanced commissioning
8.3 Sequence control when switching the motor on and o
Distributed converter for SIMOGEAR geared motors