Table 8-22 Set three-wire control, enable/ON/reverse in quick commissioning
Parameter Description
p0015 = 20 Macro drive unit
Assigning digital inputs to the commands:
Digital input 0: Enable/OFF1
Digital input 1: ON
Digital input 2: Reversing
Wiring example for the factory settings (Page 80)
Parameter
Parameter Description Factory setting
r0722.0…n CO/BO: CU digital inputs, status -
p0840[C] BI: ON/OFF (OFF1) 0
p1113[C] BI: Setpoint inversion 0
p3330[C] BI: 2/3 wire control command 1 0
p3331[C] BI: 2/3 wire control command 2 0
p3332[C] BI: 2/3 wire control command 3 0
r3333.0…n CO/BO: 2/3 wire control control word -
p3334 2/3 wire control selection
4: Three-wire control enable/ON/reverse
0
Advanced commissioning
8.5 Controlling clockwise and counter-clockwise rotation via digital inputs
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 181

Table of Contents