Bit Signicance Remarks Signal inter‐
connection
in the con‐
verter
Telegram 20 All other tele‐
grams
5 1 = OFF3 inactive Quick stop is not active. p2080[5] =
r0899.5
6 1 = Switching on inhibited active It is only possible to switch on the motor after
an OFF1 followed by ON.
p2080[6] =
r0899.6
7 1 = Alarm active Motor remains switched on; no acknowledge‐
ment is necessary.
p2080[7] =
r2139.7
8 1 = Speed deviation within the tol‐
erance range
Setpoint / actual value deviation within the tol‐
erance range.
p2080[8] =
r2197.7
9 1 = Master control requested The automation system is requested to accept
the converter control.
p2080[9] =
r0899.9
10 1 = Comparison speed reached or
exceeded
Speed is greater than or equal to the corre‐
sponding maximum speed.
p2080[10]
= r2199.1
11 1 = current or
torque limit
reached
1 = torque limit
reached
Comparison value for current or torque has
been reached or exceeded.
p2080[11]
= r0056.13 /
r1407.7
12 ---
1)
1 = Holding
brake open
Signal to open and close a motor holding brake. p2080[12]
= r0899.12
13 0 = Alarm, motor overtemperature -- p2080[13]
= r2135.14
14 1 = Motor rotates clockwise Internal converter actual value > 0. p2080[14]
= r2197.3
0 = Motor rotates counter-clock‐
wise
Internal converter actual value < 0.
15 1 = CDS display 0 = Alarm, con‐
verter thermal
overload
p2080[15]
= r0836.0 /
r2135.15
1)
If you change over from another telegram to telegram 20, then the assignment of the previous
telegram is kept.
Control word 3 (STW3)
Bit Signicance Explanation Signal interconnec‐
tion in the converter
1)
Telegram 350
0 1 = xed setpoint bit 0 Selects up to 16 dierent xed
setpoints.
p1020[0] = r2093.0
1 1 = xed setpoint bit 1 p1021[0] = r2093.1
2 1 = xed setpoint bit 2 p1022[0] = r2093.2
3 1 = xed setpoint bit 3 p1023[0] = r2093.3
4 1 = DDS selection bit 0 Changes over between settings
for dierent motors (drive data
sets).
p0820 = r2093.4
5 1 = DDS selection bit 1 p0821 = r2093.5
6 Not used
7 Not used
8 1 = technology controller enable -- p2200[0] = r2093.8
9 1 = enable DC braking -- p1230[0] = r2093.9
10 Not used
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors