EasyManua.ls Logo

Siemens SINAMICS G110M - Page 191

Siemens SINAMICS G110M
428 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Bit Meaning Explanation Signal inter‐
connection
in the con‐
verter
Telegram 20 All other tele‐
grams
5 0 = Stop RFG The output of the ramp-function generator
stops at the actual value.
p1141[0] =
r2090.5
1 = Enable RFG The output of the ramp-function generator fol‐
lows the setpoint.
6 0 = Inhibit setpoint The converter brakes the motor with the ramp-
down time p1121 of the ramp-function gener‐
ator.
p1142[0] =
r2090.6
1 = Enable setpoint Motor accelerates with the ramp-up time p1120
to the setpoint.
7 0 → 1 = Acknowledge faults Acknowledge fault. If the ON command is still
active, the converter switches to the "switching
on inhibited" state.
p2103[0] =
r2090.7
8, 9 Reserved
10 0 = No control via PLC Converter ignores the process data from the
󹪝eldbus.
p0854[0] =
r2090.10
1 = Control via PLC Control via 󹪝eldbus, converter accepts the proc‐
ess data from the 󹪝eldbus.
11 1 = Direction reversal Invert setpoint in the converter. p1113[0] =
r2090.11
12 Not used
13 ---
1)
1 = MOP up Increase the setpoint saved in the motorized po‐
tentiometer.
p1035[0] =
r2090.13
14 ---
1)
1 = MOP down Reduce the setpoint saved in the motorized po‐
tentiometer.
p1036[0] =
r2090.14
15 CDS bit 0 Reserved Changes over between settings for di󹪜erent op‐
eration interfaces (command data sets).
p0810 =
r2090.15
1)
If you change over from another telegram to telegram 20, then the assignment of the previous
telegram is kept.
Status word 1 (ZSW1)
Bit Meaning Remarks Signal inter‐
connection
in the con‐
verter
Telegram 20 All other tele‐
grams
0 1 = Ready for switching on Power supply switched on; electronics initial‐
ized; pulses locked.
p2080[0] =
r0899.0
1 1 = Ready Motor is switched on (ON/OFF1 = 1), no fault is
active. With the command "Enable operation"
(STW1.3), the converter switches on the motor.
p2080[1] =
r0899.1
2 1 = Operation enabled Motor follows setpoint. See control word 1,
bit 3.
p2080[2] =
r0899.2
3 1 = Fault active The converter has a fault. Acknowledge fault
using STW1.7.
p2080[3] =
r2139.3
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 189

Table of Contents

Other manuals for Siemens SINAMICS G110M

Related product manuals