Bit Meaning Explanation Signal interconnec‐
tion in the converter
1)
Telegram 350
4 1 = DDS selection bit 0 Changes over between settings
for dierent motors (drive data
sets).
p0820 = r2093.4
5 1 = DDS selection bit 1 p0821 = r2093.5
6 Not used
7 Not used
8 1 = technology controller enable -- p2200[0] = r2093.8
9 1 = enable DC braking -- p1230[0] = r2093.9
10 Not used
11 1 = Enable droop Enable or inhibit speed control‐
ler droop.
p1492[0] = r2093.11
12 1 = torque control active
0 = speed control active
Changes over the control mode
for vector control.
p1501[0] = r2093.12
13 1 = no external fault
0 = external fault is active (F07860)
-- p2106[0] = r2093.13
14 Not used
15 1 = CDS bit 1 Changes over between settings
for dierent operation interfaces
(command data sets).
p0811[0] = r2093.15
1)
If you switch from telegram 350 to a dierent one, then the converter sets all interconnections p1020,
… to "0". Exception: p2106 = 1.
Advanced commissioning
8.6 Drive control via PROFIBUS or PROFINET
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 191