AS-i.P3 AS-i.P2 AS-i.P1 AS-i.P0 Scaling factor Frequency (Hz)
0 0 0 1 0.07 3.5
0 0 0 0 0.05 2.5
Fixed speeds - Dual Slave
Table 8-35 Fixed speeds via the motor control bits and response in the converter
AS-i.DO2 AS-i.DO1 AS-i.DO0 Response in the converter
0 0 0 OFF1
0 0 1 On + xed speed 1 (factory setting: 1500 rpm)
0 1 0 On + xed speed 2 (factory setting: -1500 rpm)
0 1 1 On + xed speed 3 (factory setting: 300 rpm)
1 0 0 On + xed speed 4 (factory setting: 450 rpm)
1 0 1 On + xed speed 5 (factory setting: 600 rpm)
1 1 0 On + xed speed 6 (factory setting: 750 rpm)
1 1 1 Acknowledge fault or OFF2
Alarm and fault messages
Table 8-36 Alarm and fault messages via RP0 … RP3 from the converter to the AS-i master
RP3 RP2 RP1 RP0 AS-i.P0 = 0 -> alarm messages AS-i.P0 = 1 -> faults
0 0 0 0 No alarm No fault
0 0 0 1 not used Temperature rise F30004, F30012,
F30013, F30024, F30025, F30036
0 0 1 0 not used not used
0 0 1 1 No load (A07929) not used
0 1 0 0 Temperature rise (A05000,
A05004, A05006, A07012,
A07015)
I
2
t overload (F30005, F07936)
0 1 0 1 Overvoltage (A07400, A30502) Equipment malfunction (F01000 ...
F01257)
0 1 1 0 Keyswitch o (A03560)
1)
not used
0 1 1 1 Undervoltage (A07402, A30016) Motor-PTC sensor malfunction (F07011,
F07016)
1 0 0 0 I
2
t overload (A07805) Overvoltage (F30002, F30011)
1 0 0 1 not used not used
1 0 1 0 LOCAL Mode active (A03561)
1)
not used
1 0 1 1 not used Undervoltage (F30003, F07802)
1 1 0 0 not used Short-circuit at the output (F30001,
F30017, F30021, F07801, F07807,
F07900)
1 1 0 1 Motor phase loss (A30015)
2)
Motor phase loss (F30015, F07902)
Advanced commissioning
8.7 Control via AS-i
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 213