5. Evaluate your drive response.
If the motor decelerates too slowly, then reduce the ramp-down time.
The minimum ramp-down time that makes sense depends on your particular application.
Depending on the Power Module used, for an excessively short ramp-down time, the
converter either reaches the motor current, or the DC link voltage in the converter
becomes too high.
Extend the ramp-down time if the motor is braked too quickly or the converter goes into
a fault condition when braking.
6. Repeat steps 1 … 5 until the drive behavior meets the requirements of the machine or plant.
You have set the extended ramp-function generator.
Basic ramp-function generator
5DPSXSWLPH
5DPSGRZQ
WLPH
0D[LPXP
VSHHG
\
W
[
[\
W

[
\
[
\
W
\\[[
[
[
When compared to the extended ramp-function generator, the basic ramp-function generator
has no rounding times.
Parameter
Table 8-59 Parameters for setting the ramp-function generator
Parame‐
ter
Description Factory setting
p1082[D] Maximum speed 1500 rpm
p1115 Ramp-function generator selection 1
p1120[D] Ramp-function generator ramp-up time 10 s
p1121[D] Ramp-function generator ramp-down time 10 s
p1135[D] OFF3 ramp-down time 30 s
Advanced commissioning
8.17 Setpoint calculation
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 277