Pt1000 sensor
Using a Pt1000 sensor, the converter monitors the motor temperature and the sensor itself for
wire breakage and/or short-circuit:
• Temperature monitoring:
Using a Pt1000 sensor, the converter evaluates the motor temperature in the range from
-48 °C ... +248 °C.
Set the temperature for the alarm and fault thresholds with parameter p0604 or p0605.
– Overtemperature alarm (A07910):
- motor temperature > p0604 and p0610 = 0
– Overtemperature fault (F07011):
The converter responds with a fault in the following cases:
- motor temperature > p0605
- motor temperature > p0604 and p0610 > 0
• Sensor monitoring (A07015 or F07016):
– Wire-break:
The converter interprets a resistance > 2120 Ω as a wire-break and outputs the alarm
A07015. After 100 milliseconds, the converter changes to the fault state with F07016.
– Short-circuit:
The converter interprets a resistance < 603 Ω as a short-circuit and outputs the alarm
A07015. After 100 milliseconds, the converter changes to the fault state with F07016.
Parameter
Parameter Description Factory setting
p0335[[M] Type of motor cooling 0
p0601[0…n] Motor temperature sensor type 0
p0604[0…n] Mot_temp_mod 2/sensor alarm threshold 130 °C
p0605[M] Mot_temp_mod 1/2/sensor threshold and temperature value 145 °C
p0610[M] Motor overtemperature response 12
p0640[D] Current limit 0 Arms
Additional information on the motor temperature monitoring can be found in function
diagram 8016 of the List Manual.
Advanced commissioning
8.23 Motor protection with temperature sensor
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 325