Number Name Factory setting
p2185[D] Load monitoring, torque threshold 1, upper 10000000 Nm
p2186[D] Load monitoring torque threshold 1, lower 0 Nm
p2187[D] Load monitoring torque threshold 2, upper 10000000 Nm
p2188[D] Load monitoring torque threshold 2, lower 0 Nm
p2189[D] Load monitoring torque threshold 3, upper 10000000 Nm
p2190[D] Load monitoring torque threshold 3, lower 0 Nm
p2191[D] Load monitoring torque threshold, no load 0 Nm
p2192[D] Load monitoring, delay time 10 s
p2193[D] Load monitoring conguration 1
Overview
In applications with fans, pumps or compressors with the ow characteristic, the torque follows
the speed according to a specic characteristic. An insucient torque for fans indicates that the
power transmission from the motor to the load is interrupted. For pumps, insucient torque can
indicate a leakage or dry-running.
Function description
6SHHG>USP@
SVSHHGWKUHVKROG6SHHGWKUHVKROGS
6SHHGWKUHVKROGS
SPD[LPXPVSHHG
7RUTXHWKUHVKROGQRORDGS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGORZHUS
%ORFNLQJPRQLWRULQJWKUHVKROGS
%ORFNLQJPRQLWRULQJS
7RUTXH>1P@
'U\UXQQLQJSURWHFWLRQRU
EURNHQEHOW
'U\UXQQLQJSURWHFWLRQRU
EURNHQEHOW
/HDNDJHSXPSV/HDNDJHSXPSV
%ORFNHG%ORFNHG
If the torque and speed lie in the impermissible range longer than time p2192, the converter
reacts as specied in p2181.
For applications with pumps, the converter detects the following states of the driven load:
• Blocked
• Leakage
• Dry running
For applications with fans or compressors, the converter detects the following states of the
driven load:
• Blocked
• Torn belt
The monitoring is not active below speed threshold 1 and above speed threshold 3.
Advanced commissioning
8.27 Monitoring the driven load
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 333