Setting fan and compressor monitoring
1. Set p2193 = 5.
2. The converter sets the monitoring as shown.
,ISS಺WKHQS S಺
,ISุS಺WKHQS SbUSP
6SHHG>USP@
'U\UXQQLQJSURWHFWLRQ
RUWRUQEHOW
S SbUSP
%ORFNHG
S SbUSP
7RUTXH>1P@
S U಺
S U
S PLQ
S S S 
Figure 8-76 Default settings for fans and compressors
3. The converter sets monitoring response p2181 = 7
4. If necessary, adjust the speed thresholds p2182 … p2184.
5. Set the torque threshold for each speed.
The converter displays the current torque in r0031.
You have now set monitoring.
Parameter
Number Name Factory setting
r0031 Torque actual value, smoothed -
p0311[M] Rated motor speed 0 rpm
r0333[M] Rated motor torque -
p1080[D] Minimum speed 0 rpm
p1082[D] Maximum speed 1500 rpm
p1300[D] Open-loop/closed-loop control operating mode See parameter list
p2165[D] Load monitoring blocking monitoring threshold, upper 0 rpm
p2168[D] Load monitoring blocking monitoring torque threshold 10000000 Nm
p2181[D] Load monitoring, response 0
p2182[D] Load monitoring, speed threshold 1 150 rpm
p2183[D] Load monitoring, speed threshold 2 900 rpm
p2184[D] Load monitoring, speed threshold 3 1500 rpm
p2186[D] Load monitoring torque threshold 1, lower 0 Nm
p2188[D] Load monitoring torque threshold 2, lower 0 Nm
p2190[D] Load monitoring torque threshold 3, lower 0 Nm
p2191[D] Load monitoring torque threshold, no load 0 Nm
Advanced commissioning
8.27 Monitoring the driven load
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 335