The motor operates in partial load mode between no-load operation and the rated motor torque.
Depending on p1580, in the partial load range, the converter reduces the ux setpoint linearly
with the torque.
)OX[
(IILFLHQF\
S
S
S
Figure 8-81 Qualitative result of eciency optimization, method 1
The reduced ux in the motor partial load range results in higher eciency.
Parameters
Table 8-76 Eciency optimization, method 2
Number Name Factory setting
p1401[D] Flux control conguration 0000 0000 0000
0110 bin
p1570[D] CO: Flux setpoint 100%
p3315[D] Eciency optimization 2 minimum ux limit value 50%
p3316[D] Eciency optimization 2 maximum ux limit value 110 %
Table 8-77 Eciency optimization, method 1
Number Name Factory setting
p1570[D] CO: Flux setpoint 100%
p1580[D] Eciency optimization 80%
Advanced commissioning
8.28 Eciency optimization
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 339