Flow characteristic
6SHHGLQ
3RZHULQ
6SHHGSRZHU






SS
SS
SS
SS
SS
Figure 8-84 Factory setting of the 󹪞ow characteristic
To set the characteristic, you require the following data from the machine manufacturer for each
speed interpolation point:
The 󹪞ow rate of the 󹪞uid-󹪞ow machine associated with the 5 selected converter speeds
At constant speed, the power drawn which is associated with the 5 󹪞ow rates corresponds to
the line frequency and mechanical throttling of the 󹪞ow rate.
Parameters
Number Name Factory setting
r0039[0...n] CO: Energy display -
p0040 Reset energy consumption display 0
r0041 Energy saved -
r0042[0...n] CO: Process energy display -
p0043 BI: Energy consumption display enabled. 0
p3320[0…n] Fluid 󹪞ow machine power, point 1 25
p3321[0…n] Fluid 󹪞ow machine speed, point 1 0
p3322[0…n] Fluid 󹪞ow machine power, point 2 50
p3323[0…n] Fluid 󹪞ow machine speed, point 2 25
p3324[0…n] Fluid 󹪞ow machine power, point 3 77
p3325[0…n] Fluid 󹪞ow machine speed, point 3 50
p3326[0…n] Fluid 󹪞ow machine power, point 4 92
p3327[0…n] Fluid 󹪞ow machine speed, point 4 75
p3328[0…n] Fluid 󹪞ow machine power, point 5 100
p3329[0…n] Fluid 󹪞ow machine speed, point 5 100
Advanced commissioning
8.29 Calculating the energy saving for 󹪞uid 󹪞ow machines
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 341