Selecting the number of drive data sets
The number of drive data sets (1 ... 4) is dened by parameter p0180.
Parameter Description
p0010 = 0 Drive commissioning: Ready
p0010 = 15 Drive commissioning: Data sets
p0180 Number of Drive Data Sets (DDS)
Copying the drive data sets
Parameter Description
p0819[0] Source drive data set
p0819[1] Target drive data set
p0819[2] = 1 Starts the copy operation
Parameter
Parameter Description Factory setting
p0010 Drive commissioning parameter lter 1
r0051 CO/BO: Drive data set DDS eective -
p0180 Number of Drive Data Sets (DDS) 1
p0819[0 … 2] Copy drive data set DDS 0
p0820[C] BI: Drive data set DDS selection, bit 0 0
p0821[C] BI: Drive data set DDS selection, bit 1 0
p0826[M] Motor changeover, motor number 0
Further information
The converter switches the motor data set (MDS) and the power unit data set (PDS) together
with the drive data set (DDS).
Advanced commissioning
8.30 Switchover between dierent settings
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 343