Selecting the number of drive data sets
The number of drive data sets (1 ... 4) is de󹪝ned by parameter p0180.
Parameter Description
p0010 = 0 Drive commissioning: Ready
p0010 = 15 Drive commissioning: Data sets
p0180 Number of Drive Data Sets (DDS)
Copying the drive data sets
Parameter Description
p0819[0] Source drive data set
p0819[1] Target drive data set
p0819[2] = 1 Starts the copy operation
Parameter
Parameter Description Factory setting
p0010 Drive commissioning parameter 󹪝lter 1
r0051 CO/BO: Drive data set DDS e󹪜ective -
p0180 Number of Drive Data Sets (DDS) 1
p0819[0 … 2] Copy drive data set DDS 0
p0820[C] BI: Drive data set DDS selection, bit 0 0
p0821[C] BI: Drive data set DDS selection, bit 1 0
p0826[M] Motor changeover, motor number 0
Further information
The converter switches the motor data set (MDS) and the power unit data set (PDS) together
with the drive data set (DDS).
Advanced commissioning
8.30 Switchover between di󹪜erent settings
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 343