Number Cause Remedy
F07902 Motor stalled Check whether the motor data has been parameterized correctly and per‐
form motor identication.
Check the current limits (p0640, r0067, r0289). If the current limits are too
low, the drive cannot be magnetized.
Check whether motor cables are disconnected during operation.
A07903 Motor speed deviation Increase p2163 and/or p2166.
Increase the torque, current and power limits.
A07910 Motor overtemperature Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 or Pt1000 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
A07920 Torque/speed too low The torque deviates from the torque/speed envelope curve.
• Check the connection between the motor and the load.
• Adapt the parameterization corresponding to the load.
A07921 Torque/speed too high
A07922 Torque/speed out of tolerance
F07923 Torque/speed too low
• Check the connection between the motor and the load.
• Adapt the parameterization corresponding to the load.
F07924 Torque/speed too high
A07927 DC braking active Not required
A07980 Rotary measurement activated Not required
A07981 No enabling for rotary measurement Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
A07991 Motor data identication activated Switch on the motor and identify the motor data.
F08501 Setpoint timeout
• Check the PROFINET connection.
• Set the controller to RUN mode.
• If the error occurs repeatedly, check the set monitoring time p2044.
F08502 Monitoring time sign-of-life expired
• Check the PROFINET connection.
F08510 Send conguration data not valid
• Check the PROFINET conguration
A08511 Receive conguration data not valid
A08526 No cyclic connection
• Activate the controller with cyclic operation.
• Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565 Consistency error aecting adjusta‐
ble parameters
Check the following:
• IP address, subnet mask or default gateway is not correct.
• IP address or station name used twice in the network.
• Station name contains invalid characters.
F13100 Know-how protection: Copy protec‐
tion error
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
• Insert a suitable memory card and switch the converter supply voltage
temporarily o and then on again (POWER ON).
• Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy protec‐
tion cannot be activated
Insert a valid memory card.
Alarms, faults and system messages
9.7 List of alarms and faults
Distributed converter for SIMOGEAR geared motors
360 Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL