6. The converter transfers the 󹪝rmware from the memory card into its memory.
The transfer takes between 5 and 10 minutes.
While data is being transferred, the LED RDY on the converter stays red. The BF LED 󹪞ashes
orange with a variable frequency.
99
5'<
%)
%)
5'<
PLQ
7. Once the transfer is completed, the RDY and BF LEDs 󹪞ash slowly red (0.5 Hz).
Note
Damaged 󹪝rmware due to a supply voltage interruption during transfer
If the power supply fails during the transfer, this can damage the converter's 󹪝rmware.
Do not switch o󹪜 the converter's supply voltage while the transfer is running.
8. Switch o󹪜 the 24 V or the 400 V supply voltage of the converter.
9

9. Remove the Power Module.
10.Withdraw the card with the 󹪝rmware from the Power Module.
Corrective maintenance
10.4 Firmware upgrade and downgrade
Distributed converter for SIMOGEAR geared motors
Operating Instructions, 10/2020, FW V4.7 SP13, A5E31298649B AL 381