Communication
11.1 Integration in SIMATIC S7-1200
SIWAREX WP241
160 Manual, 04/2014, A5E33713528A
11.1.6
Error codes of function block
Table 11- 3 Statuses/errors when working with the function block
Error bit
Error description
bo_ApplIDError
Address module does not match the function block
bo_ApplIDDRError
Data record does not match the inserted module
bo_SFBError
Runtime error during transmission of data record
bo_RdPerError
Reading of I/O data failed
bo_LifeBitError
SIWAREX no longer responds
bo_StartUpError
Command was sent although StartUp is still TRUE
bo_WrongFW
Data record version does not match the firmware
bo_InvalidCMD
An invalid command code was sent
bo_DataOperationError
Synchronous data operation error has occurred
bo_StartUp
Startup synchronization of module running
Note
If execution of the function block is faulty, the variables shown do not correspond to the
actual status in the module.