9.5 Message list
SIWAREX WP241
142 Manual, 04/2014, A5E33713528A
9.5.2
Technology error message list
Technology error (code 2000 to 4999)
Error code
Description and remedy
2000 Technology error
2000
Group message, at least one technology error exists
2002 Trace error 2002 The set recording rate for trace function cannot be processed. Set
a slower recording rate.
2003 Zeroing aborted 2003 The zeroing procedure has been canceled. Possible causes:
violation of zeroing limits.
2004 Trace memory full 2004 The trace recording has been cancelled. Possible causes: trace
memory full and not declared as ring memory.
3001 Totalizer error
3001
Fault occurred during totalizing.
3002 Calibration procedure interrupted 3002 Current calibration procedure has been aborted. Possible causes:
non-plausible values have been determined during the command.
9.5.3
Data and operating errors message list
Data and operating errors
(code 5000 to 8999)
Error code
Description and remedy
5000 Data and operating error exists
5000
Group error, a bit is set in the data and operating error bits
5001 Command code or data record
unknown
5001 Command code or data record is not known with current
application
5002 Command or data change not
possible because write protection is active
5002 The command or changing of data is not possible due to write
protection. The data record was rejected.
5003 Cannot exit service mode
5003
Cannot exit calibration mode; calibration incomplete
5004 Command or data transmission only
available in service mode
5004 Activation of service mode is required to execute command or
transmit data
5006 Command or data transmission not
possible because of BUSY
5006 Command can currently not be executed because module is
BUSY (data record or command transmission already active,
…)
5007 Command or data transmission not
possible because module is faulty or
SIMATIC CPU stop
5007 Command can currently not be executed because of a
problem or SIMATIC CPU stop
5104 Command not possible because
range is exceeded
5104 Command (e.g. set to zero, tare, calibrate command) cannot
be executed because the permitted range has been
exceeded. The ranges are defined in DR 3.
5105 Load cell parameters not plausible 5105 Load cell parameters in data record DR 10 are not plausible
(number, support points, load specifications, etc.).
5108 ID does not exist
5108
Requested logbook ID not present in memory.
5199 Error in command to DI 5199 Processing of a command triggered at the DIs is not possible.
The cause can be determined in data record DR 32.
6002 Logging not possible because weight
is too small
6002 Logging is not possible because the limits for the minimum
weight or maximum weight were not observed.
6003 Command cannot be executed since
a dynamic procedure is already active
6003 Desired command cannot be executed since a dynamic
command (calibration, zeroing) is already being executed.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIWAREX WP241 and is the answer not in the manual?

Siemens SIWAREX WP241 Specifications

General IconGeneral
BrandSiemens
ModelSIWAREX WP241
CategoryAccessories
LanguageEnglish

Related product manuals