Function Factory-preset value Adjusted value
Heat/Cool recovery
Carry over control
Carry over control
On
X
Off
On Off
Defrosting
Defrosting
On
X
Off
On Off
Defrosting limit value Pa 50
Calibration
On
X
Off
On Off
Type of heat exchanger (CX)
Type of heat exchanger
Fixed-speed cont-
rolled pump
X
Pressure-controlled
pump
Fixed-speed cont-
rolled pump
Pressure-controlled
pump
Glycol (CX)
Type of glycol
X
Ethylene
Propylene Ethylene Propylene
Content of glycol
20
X
30
40 20 30 40
Calibration/Optimization (PX)
Calibration
On
X
Off
On Off
Bypass optimization
On
X
Off
On Off
Heat exchanger
Outdoor air limits
Step 1 °C 15
Step 2 °C 18
Step 3 °C 20
Air fl ow, limits
Cooling, 0-10 V
Supply air, 0-10 V 25% of max. airfl ow for air handling unit
Extract air, 0-10 V 25% of max. airfl ow for air handling unit
Cooling, On/Off
Supply air, On/Off, step 1 25% of max. airfl ow for air handling unit
Extract air, On/Off, step 1 25% of max. airfl ow for air handling unit
Supply air, On/Off, step 2 50% of max. airfl ow for air handling unit
Extract air, On/Off, step 2 50% of max. airfl ow for air handling unit
Supply air, On/Off, step 3 75% of max. airfl ow for air handling unit
Extract air, On/Off, step 3 75% of max. airfl ow for air handling unit