Function Factory-preset value Adjusted value
SMART Link
Type of unit X
Inactive
Water, heat pump Inactive Water, heat pump
Water, chiller Water, reversible Water, chiller Water, reversible
DX, heat pump DX, chiller DX, heat pump DX, chiller
DX, reversible DX, reversible
Water
Heated water (set point) °C 40
Heated water diff K 3
Chilled water (set point) °C 12
Chilled water diff K 2
Outdoor air limit
(not applicable to the
chiller)
°C -20
Optimize
On
X
Off
On Off
Cool. optim, reg. speed K/min 0.3
Heat. optim. reg. speed K/min 0.3
Valve limit, lower % 75
Valve limit, upper % 95
Delay s 60
AQUA Link
On
X
Off
On Off
Pump alarm
X
Inactive
Alarm on closed contact Inactive Alarm on closed contact
Alarm on open contact Contactor function Alarm on open contact Contactor function
DX (Celest+)
Amount of units 1
Comfort mode, durationmin
30
Outdoor air limit
(not applicable to the
chiller)
°C -20
Defrost delay s
180
Dead band,
supply air temp.
K
1,0
Stabilization time s
240