GB.GOLDSKE.160901
www.swegon.com 153
We reserve the right to alter specifi cations without notice.
Function Factory-preset value Adjusted value
Humidity
Humidifying
Humidifying
X
Inactive
On/Off Inactive On/Off
0 - 10 V 0 - 10 V
Location, regulating
humidity sensor
X
Supply air
Extract air Supply air Extract air
Evaporative
Start limit %RH 40
Stop limit %RH 45
Steam
Set point %RH 30
Max. supply air %RH 80
Dehumidifying
Dehumidifi cation
X
Inactive
Supply air
Inactive
Supply air
Extract air Extract air
Supply air, rel. humidity %RH 50
Extract air, rel. humidity %RH 50
Humidifi er alarm
Alarm input
X
Inactive
Closed circuit Inactive Closed circuit
Open circuit Contactor function Open circuit Contactor function
Humidity
ReCO
2
Function Factory-preset value Adjusted value
ReCO2
CO
2
/VOC, operating
mode
X
Inactive
CO
2
/VOC Inactive CO
2
/VOC
CO
2
/VOC and air fl ow boost CO
2
/VOC and air fl ow boost
Temperature mode
X
Inactive
Heat sequence Inactive Heat sequence
Cool sequence Heat and cool sequence Cool sequence Heat and cool sequence
CO
2
/VOC
CO
2
, set point % 50
CO
2
, set point ppm 1000
VOC, set point ppm 1500
Min. outdoor air 25% of max. airfl ow for air handling unit
Min. exhaust air 25% of max. airfl ow for air handling unit
Calibration
On
X
Off
On Off
Temperature
Min. outdoor air 25% of max. airfl ow for air handling unit
Min. exhaust air 25% of max. airfl ow for air handling unit
Calibration
On
X
Off
On Off