GB.GOLDSKE.160901
154 www.swegon.com
We reserve the right to alter specifi cations without notice.
All Year
Comfort
Function Factory-preset value Adjusted value
All Year Comfort
Function X
Inactive
Chilled water Inactive Chilled water
Heated water Chilled and heated water Heated water Chilled and heated water
Chilled water
Chilled water °C 14
Outdoor temp. comp.
On
X
Off
On Off
Outdoor temp. X1 °C 10
Outdoor temp. X2 °C 20
Outdoor temp. X3 °C 25
Outdoor temp. X4 °C 30
Chilled water temp. Y1 °C 22
Chilled water temp Y2 °C 18
Chilled water temp. Y3 °C 14
Chilled water temp. Y4 °C 12
Outd. temp. for pump start °C 10
Outd. temp. for pump stop °C 7
Room temp. compensation
On
X
Off
On Off
Room temp. set point °C 21
Room temp. P-band K 5
Room comp. night block.
On
X
Off
On Off
Night compensation
On
X
Off
On Off
Night reduction K 2
Time channel 1, start night h:min. 00:00
Time channel 1, end night h:min. 00:00
Time channel 1, period
X
Inactive
Monday Inactive Monday
Tuesday Wednesday Tuesday Wednesday
Thursday Friday Thursday Friday
Saturday Sunday Saturday Sunday
Mon.-Fri. Mon.-Sun. Mon.-Fri. Mon.-Sun.
Sat.-Sun. Sat.-Sun.
Dew point compensation
On
X
Off
On Off
Air fl ow compensation
On
X
Off
On Off
Periodic operation pump
X
On
Off On Off
Periodic operation valve
On
X
Off
On Off
Periodic operation interval h 24
Periodic operation period min. 3
Pump alarm
X
Inactive
Alarm on closed cont. Inactive Alarm on closed cont.
Alarm on open contact Alarm on open contact
Contactor function Contactor function
Valve alarm
On
X
Off
On Off