GB.GOLDSKE.160901
www.swegon.com 155
We reserve the right to alter specifi cations without notice.
Function Factory-preset value Adjusted value
Heated water
Heated water °C 30
Outdoor temp. comp.
On
X
Off
On Off
Outdoor temperature X1 °C -20
Outdoor temperature X2 °C 0
Outdoor temperature X3 °C 5
Outdoor temperature X4 °C 15
Heated water temp. Y1 °C 40
Heated water temp. Y2 °C 30
Heated water temp. Y3 °C 20
Heated water temp. Y4 °C 15
Outd. temp. for pump start °C 15
Outd. temp. for pump stop °C 18
Room temp. compensation
On
X
Off
On Off
Room temp. set point °C 21
Room temp. P-band K 5
Room comp. night blocking
On
X
Off
On Off
Night compensation
On
X
Off
On Off
Night reduction K -2
Time channel 2, start night h:min. 00:00
Time channel 2, end night h:min. 00:00
Time channel 2, period
X
Inactive
Monday Inactive Monday
Tuesday Wednesday Tuesday Wednesday
Thursday Friday Thursday Friday
Saturday Sunday Saturday Sunday
Mon.-Fri. Mon.-Sun. Mon.-Fri. Mon.-Sun.
Sat.-Sun. Sat.-Sun.
Air fl ow compensation
On
X
Off
On Off
Periodic operation pump
X
On
Off On Off
Periodic operation valve
On
X
Off
On Off
Periodic operation interval h 24
Periodic operation period min 3
Pump alarm
X
Inactive
Alarm on closed cont. Inactive Alarm on closed cont.
Alarm on open contact Alarm on open contact
Contactor function Contactor function
Valve alarm
On
X
Off
On Off
MIRU Control
Function Factory-preset value Adjusted value
MIRU Control
See the commissioning report for MIRU Control