097-72020-01 Revision K – December 2005 TimeSource 3100 User’s Guide 79
Chapter 3 Installing the TimeSource 3100
Powering Up the Shelf
If these values require change, use the Edit Communication command to set
communications parameters for TL1 communications.
ED-COM::COM-5551:<ctag>:::[MONMSG=b[,]][KEEPALIVE=c[,]]
[ENDOFTEXT=d[,]][ECHO=b[,]][COMPRI=e[,]][AUTOLOGOFF=c[,]]
[SWCONTROL=b];
where:
MONMSG=b Monitors messages on all ports (b = ALW), or current port (b = INH)
KEEPALIVE=c Inactive minutes until the unit sends a COMPLD message to
keep the connection from being closed (c = 0 to 255)
ENDOFTEXT=d Hex code added to responses before semicolon (d = 0
(disabled) to 9F)
ECHO=b Echoes characters received so they appear on the user's screen as
typed (b = ALW), or inhibits echo (b = INH)
COMPRI=e Sets the communication port capabilities as follows:
ALW0 = normal communication, no autonomous messages
ALW1 = normal communication, autonomous messages
ALW2 = autonomous messages received, logged on or not
INH = closes connection and keeps port from use (command must go to
another port) (if the port is in use, this command also logs off the user)
AUTOLOGOFF=c Inactive minutes until the unit logs off the user, keeping the
connection open (c = 0 to 255)
SWCONTROL=b Uses software (XON/XOFF) flow control (b = ALW), or no flow
control (b = INH)
Set the ESCIU Parameters
29.If you are not using ESCIU ports, skip to Step 31. Use the Edit Equipment
command to specify how the ESCIU performs during holdover:
ED-EQPT::TS3100:<ctag>:::BYPASS=a;
where:
a = E1 traffic bypasses the ESCIU circuitry (a=ALW) or continues to be
synchronized during holdover (a=INH)
30.Use the Edit Equipment command to specify how the ESCIU performs with a
Loss-of-Signal (LOS) alarm on the incoming span:
ED-EQPT::OPT-a:<ctag>::ALMOUT=b;
where:
a = Directs this command to ESCIU span 1 (a=1) or span 2 (a=2)
b = If LOS is detected on the incoming span, the ESCIU passes AIS
downstream (b=AIS) or passes the LOS downstream (b=PASSTHRU)

Table of Contents

Other manuals for Symmetricom TimeSource 3100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Symmetricom TimeSource 3100 and is the answer not in the manual?

Symmetricom TimeSource 3100 Specifications

General IconGeneral
BrandSymmetricom
ModelTimeSource 3100
CategoryGPS
LanguageEnglish

Related product manuals