Switch-on Unsafe Channels Permanently (1. and 2. OSSD)
The unsafe channels at C4 - C7 of the device can be safe switched off via the internal safety outputs
FSO0 and FSO1. If they have to be switched on permanently, then FSO0 and FSO1 need a permanent
switch-on condition (TRUE). The programming is done in the 1. and 2. OSSD.
Delete the element "CIP Safety
Input" in both OSSDs (1. and 2. OSSD) and replace it by a TRUE-
element from the device library.
Both internal outputs are perma
nently active.
Fig. 37: Permanent activation of FSO0 and FSO1.