5. In the Select File window, select the appropriate setup file and Select File.
To change the default folder for uploading setup files in AWS client, select Settings
> Options.
The setup file upload to the QML data logger starts.
When the file upload is ready, the QML data logger starts executing the new setup according
to the settings in the setup
file. Check that the static parameters are correct.
4.8.3 Cleaning AWS Settings
You can completely remove the settings of an earlier setup from the QML data logger. The
cleanup erases the following data from the QML data logger:
Static parameters and parameter sets (factory settings and calibration values are
preserved)
Log
files from /Log
The cleanup does not delete the setup
file on the QML data logger, which, after the reset,
restores the default station settings. To avoid this, delete or replace the setup file before
executing the logger content cleanup.
Erasing station settings from a remotely managed QML data logger may
render it inaccessible for further remote maintenance. Use with caution.
CAUTION!
1. In AWS Client, select Maintenance > AWS Cleanup.
2. In the confirmation window, select Yes.
3. Wait for the cleanup to complete. The cleanup includes multiple steps, and takes a
while to execute.
4.9
 Using QML Data Logger
4.9.1 Using External Memory Card
The QML logger copies or moves log files from the internal log directory to an external
CompactFlash (CF) memory card daily at midnight. The default time is 00:05:00.
Always use an external memory card in the logger, or the internal log memory may
fill up.