EasyManua.ls Logo

YASKAWA GA800

YASKAWA GA800
1078 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Standards Compliance
5
5.3 UL Standards
YASKAWA SIEPC71061737D GA800 Drive Technical Reference 283
Model Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
(mm
2
)
IP20 Applicable
Gauge
*1
AWG, kcmil
(mm
2
)
Wire Stripping
Length
*2
mm
Terminal Screw
Size and Shape
Tightening
Torque
Nm (lbfin)
4605
R/L1, S/L2, T/L3 300 × 4P
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
35
(310)
U/T1, V/T2, W/T3 300 × 4P
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
35
(310)
-, +1 400 × 4P
3/0 - 400 × 4P
(95 - 185 × 4P)
300 - 400 × 4P
(150 - 185 × 4P)
-
M12
35
(310)
+3 4/0 × 4P
2 - 4/0 × 4P
(35 - 95 × 4P)
4/0 × 4P
(95 × 4P)
-
M12
35
(310)
2/0
2/0 - 300
(70 - 150)
- -
M12
32 - 40
(283 - 354)
4720
R/L1, S/L2, T/L3 300 × 4P
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
35
(310)
U/T1, V/T2, W/T3 300 × 4P
2/0 - 300 × 4P
(70 - 150 × 4P)
250 - 300 × 4P
(120 - 150 × 4P)
-
M12
35
(310)
-, +1 400 × 4P
3/0 - 400 × 4P
(95 - 185 × 4P)
300 - 400 × 4P
(150 - 185 × 4P)
-
M12
35
(310)
+3 4/0 × 4P
2 - 4/0 × 4P
(35 - 95 × 4P)
4/0 × 4P
(95 × 4P)
-
M12
35
(310)
2/0
2/0 - 300
(70 - 150)
- -
M12
32 - 40
(283 - 354)
*1 For IP20 protection, use wires that are in the range of applicable gauges.
*2 Remove insulation from the ends of wires to expose the length of wire shown.
*3 For wire gauges more than AWG 8, tighten to a tightening torque of 4.1 N∙m to 4.5 N∙m (36 lbf∙in to 40 lbf∙in).
*4 Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
*5 A junction terminal is necessary to connect a braking resistor unit (LKEB-series) to terminals B1 and B2.
6-Phase/12-Pulse 400 V Class
Model Terminal
Recomm. Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
(mm
2
)
Wire
Stripping
Length
*1
mm
Terminal Screw
Size and Shape
Tightening Torque
Nm (lbfin)
T103
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
4 × 1P 2)
8 - 4
(10 -25)
14 M5
2.3 - 3
(20 - 27)
U/T1, V/T2, W/T3 1
3 - 3/0
(25 - 95)
24 M8
15.3
(135)
-, +3 3
14 - 1/0
(2.5 - 50)
18 M6
3.1 - 3.8
(28 - 33)
4
6 - 4
(16 - 25)
- M6
5.4 - 6
(47.8 - 53.1)
T140
R/L1, S/L2, T/L3
R1/L11, S1/L21, T1/L31
3 × 1P 2)
6 - 1/0
(16 - 50)
18 M6
3.1 - 3.8
(28 - 33)
U/T1, V/T2, W/T3 2/0
1 - 4/0
(50 - 95)
33 M8
20
(175)
-, +3 1
6 - 3/0
(16 - 95)
24 M8
15.3
(135)
4
4 - 1/0
(25 - 50)
- M8
9 - 11
(79.7 - 97.4)

Table of Contents

Other manuals for YASKAWA GA800

Related product manuals