EasyManua.ls Logo

YOKOGAWA µR1800 - Fail;Chart End Wiring

YOKOGAWA µR1800
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 - 10 IM 4H3B1-01E
3.2.5 FAIL/Chart End Wiring
1 Make sure the power switch is turned OFF and remove the transparent cover at the rear
of the µR1800.
2 Connect the FAIL/Chart end output wires to the FAIL/Chart end output terminal.
3 Replace the transparent cover.
The FAIL/Chart end terminals (option) are arranged as follows:
The FAIL/Chart End output relay is of the de-energize type. See 5.3.9 for details.
To prevent an electric shock, ensure the main power supply is turned OFF
during wiring and ensure the ground terminal is connected using a class 3
resistance of 100 or less.
Ensure the ground terminal is connected using a class 3 resistance of 100 or
less.
Use "crimp-on" lugs with insulation sleeves for all connections if a voltage of
more than 30 VAC or 60 VDC is applied to the alarm output or fail/memory end
output. Furthermore, use doubleinsulated wires (withstand voltage
performance: more than 2300VAC) for those wires which apply 30 VAC or
60VDC. All other wires can be basic-insulated (withstand voltage performance:
more than 1350VAC). To prevent electric shock, do not touch the terminal after
wiring and make sure to re-attach the cover.
NOTE To prevent an emission of electromagnetic disturbances, separate the FAIL/Chart end
wires from the power supply and input wires at least 0.1m. Over 0.5m is recommended.
Figure 3.13 FAIL/Chart End Output Terminal
!
WARNING
CHART
!
FAIL
NO NCC
NO NCC

Table of Contents

Related product manuals