7 - 17
IM 4H3B1-01E
7. BASIC SETTINGS
MENU
SETTING PROCEDURE:
Press the MENU-key for three seconds to enter the SET mode.
Select the ‘SET=RANGE’ display by using the UP/DOWN-keys.
Then press the ENT-key.
Use the UP/DOWN-keys to select the desired measuring channel.
Press the ENT-key.
Use the UP/DOWN-keys to select ‘OPT’.
Press the ENT-key.
Use the UP/DOWN-keys to select ‘RRJC’.
Press the ENT-key.
Use the UP/DOWN-keys to select the reference channel.
Press the ENT-key.
Note that the number of the reference channel must be lower than
that of the measuring channel. If not, an error will occur.
Select the minimum value of the recording span (SPAN L) using
the UP/DOWN and RIGHT-keys. Then press the ENT-key.
The display which appears will allow you to enter the maximum
value of the recording span (SPAN R). Select it the same way as
for the minimum value and press the ENT-key.
Note that the recording span cannot be beyond the input range, nor
can SPAN L be equal SPAN R.
The setting completed.
Press the ENT-key to return to the ‘2:MODE=TC’ display for
other channel using the remote RJC; or press the ESC-key to go to
the ‘SET=RANGE’ display; or press the MENU-key for three
seconds to return to the Operation mode.
SET=RANGE
SET OK
2:MODE=TC
2:MODE=OPT
2:RJC CH=1
2:LEFT= 0.0
FEED
PRINT
ALARM
ACK
MENU
ESC
3 sec
PRINT
PRINT
ALARM
ACK
MENU
ESC
**
ALARM
ACK
PRINT
ALARM
ACK
PRINT
ALARM
ACK
PRINT
ALARM
ACK
FEED
PRINT
ALARM
ACK
2:OPTION MODE=
RRJC
2:RIGHT= 800.0
3 sec
7.7 How to Set the Remote RJC (For /N5 Model)
1
2
3
4
1
2
3
4
SKIP
VOLT
TC
RTD
DI
DELT
SCL
SQRT
OPT
RRJC
MATH
SPAN-LRANGE
ALARM
UNIT
CHART
CLOCK
COPY
AUX
0.0 800.0
SPAN-R

Table of Contents