7. Connect the motor cable:
• Ground the shield 360 degrees by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable (7a).
IP66 (UL Type 4X): for best EMC performance, do not ground the shield.
The motor cable shield should only be grounded at the motor end, not at
the drive end.
• If you need more working space, open the screw (7d) and lift the EMC plate
off. Remember to put it back after you have installed motor and input
power cables.
• Connect the twisted shield of the cable to the grounding terminal (7b).
• Connect the phase conductors of the cable to the T1/U, T2/V and T3/W
terminals. Tighten the screws to the torque given in the table below (7c).
R3R1…R2
BRAKE RESINPUT
PE
MOTOR
R-
R+
UDC+
W/3TV/2TU/1T3L2L1L
7b7c
7a
MOTOR
T1/U T2/V T3/W
INPUT
L1 L2 L3
BRAKE RES
R-
R+
UDC+
PE
7b
7c
7a
R4R4 v2
7c
7b
7a
L1 L2
L3
R+
UDC+
R- T1/U T2/V T3/W
7a
7c
7b
7d
L1 L2
L3
R+
UDC+
R- T1/U T2/V T3/W
R4 v2R4R3R2R1Frame size
lbf·ftN·mlbf·ftN·mlbf·ftN·mlbf·ftN·mlbf·ftN·m
4.05.53.04.02.63.51.11.50.71.0T1/U, T2/V, T3/W
2.12.92.12.91.11.51.11.51.11.5
PE,
0.91.20.91.20.91.20.91.20.91.2
Electrical installation – Global (IEC) 143