EasyManua.ls Logo

ABB ACS580 Series - Page 143

ABB ACS580 Series
468 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7. Connect the motor cable:
Ground the shield 360 degrees by tightening the clamp of the power cable
grounding shelf onto the stripped part of the cable (7a).
IP66 (UL Type 4X): for best EMC performance, do not ground the shield.
The motor cable shield should only be grounded at the motor end, not at
the drive end.
If you need more working space, open the screw (7d) and lift the EMC plate
off. Remember to put it back after you have installed motor and input
power cables.
Connect the twisted shield of the cable to the grounding terminal (7b).
Connect the phase conductors of the cable to the T1/U, T2/V and T3/W
terminals. Tighten the screws to the torque given in the table below (7c).
R3R1…R2
BRAKE RESINPUT
PE
MOTOR
R-
R+
UDC+
W/3TV/2TU/1T3L2L1L
7b7c
7a
MOTOR
T1/U T2/V T3/W
INPUT
L1 L2 L3
BRAKE RES
R-
R+
UDC+
PE
7b
7c
7a
R4R4 v2
7c
7b
7a
L1 L2
L3
R+
UDC+
R- T1/U T2/V T3/W
7a
7c
7b
7d
L1 L2
L3
R+
UDC+
R- T1/U T2/V T3/W
R4 v2R4R3R2R1Frame size
lbf·ftN·mlbf·ftN·mlbf·ftN·mlbf·ftN·mlbf·ftN·m
4.05.53.04.02.63.51.11.50.71.0T1/U, T2/V, T3/W
2.12.92.12.91.11.51.11.51.11.5
PE,
0.91.20.91.20.91.20.91.20.91.2
Electrical installation Global (IEC) 143