IP55 (UL Type 12)IP21 (UL Type 1)IP21 (UL Type 1)
WARNING!
If you install the drive on any other system than symmetrically grounded
TN-S system, see Grounding system compatibility check (page 132) if you
have to disconnect the EMC filter and ground-to-phase varistor.
2. Attach the residual voltage warning sticker in the local language next to the
control unit.
3. Remove the shroud on the power cable terminals by releasing the clips with a
screwdriver (3a) and pulling the shroud out (3b).
Motor cable
4. Cut an adequate hole into the rubber grommet. Slide the grommet onto the
cable.
Electrical installation – Global (IEC) 149