Parameters and firmware blocks
121
Block outputs located in other
parameter groups
2.18 D2D FOLLOWER CW (page 100)
6.01 STATUS WORD 1 (page 105)
6.02 STATUS WORD 2 (page 106)
6.03 SPEED CTRL STAT (page 107)
6.05 LIMIT WORD 1 (page 107)
6.07 TORQ LIM STATUS (page 108)
6.09 POS CTRL STATUS (page 109)
6.10 POS CTRL STATUS2 (page 110)
6.11 POS CORR STATUS (page 111)
10.01 EXT1 START FUNC FW block: DRIVE LOGIC (see above)
Selects the source for the start and stop control in external control location EXT1.
Note: This parameter cannot be changed while the drive is running.
(0) Not sel No source selected.
(1) In1 Source of the start and stop commands are selected by parameter
10.02 EXT1 START IN1. The start/stop is controlled as follows:
(2) 3-wire Source of the start and stop commands are selected by parameters
10.02 EXT1 START IN1 and 10.03 EXT1 START IN2. The start/stop is
controlled as follows:
(3) FBA Start and stop control from the source selected by parameter 10.13 FB
CW USED.
(4) D2D Start and stop control from another drive via D2D Control Word.
(5) IN1 F IN2R The source selected by 10.02 EXT1 START IN1 is the forward start
signal, the source selected by 10.03 EXT1 START IN2 is the reverse
start signal.
(6) IN1S IN2DIR The source selected by 10.02 EXT1 START IN1 is the start signal
(0 = stop, 1 = start), the source selected by 10.03 EXT1 START IN2 is
the direction signal (0 = forward, 1 = reverse).
Par. 10.02 Command
0 -> 1 Start
1 -> 0 Stop
Par. 10.02 Par. 10.03 Command
0 -> 1 1 Start
Any 1 -> 0 Stop
Any 0 Stop
Par. 10.02 Par. 10.03 Command
00 Stop
10Start forward
0 1 Start reverse
11 Stop