73
Installing the Avaya G600 Media Gateway
October 2002
Connect Media Gateway Grounds and Other
Grounds
Follow these additional grounding requirements:
• The approved ground wire must be green, 6 AWG (#40) (16 square millimeters), copper,
stranded wire. This is in addition to the ground wire in the AC power cord.
• Bond all approved grounds at the single-point ground to form a single grounding
electrode system.
Connect the cable as shown in ‘‘Grounding for a single media gateway’’ on page 73
for a single
Avaya G600 Media Gateway, or ‘‘Grounding for multiple media gateways’’ on page 74
for 2 or
more Avaya G600 Media Gateways.
Grounding for a single media gateway
Figure notes
1 10 AWG (#25) (6 mm
2
) wire
to coupled bonding
conductor (CBC).
2 6 AWG (#40) (16 mm
2
) ground
wire from single-point ground
block to the approved building
ground.
1
2
cadpgnd1 LJK 102500