EasyManua.ls Logo

Avaya S8700 - Connect the Power Cords

Avaya S8700
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
75
Installing the Avaya G600 Media Gateway
October 2002
1 Connect one end of the conductor to a telephone cable building entrance protector
ground that is connected to an approved ground.
2 Route the conductor next to the exposed telephone cables being protected until it reaches
the crossconnect nearest to the telephone system.
3 Position the nonexposed telephone cables at least 12 inches (30.5 centimeters) away
from exposed telephone cables whenever possible.
4 Terminate the other end to the single-point ground block provided for the telephone
system.
Connect the Power Cords
!
WARNING:
The AC power cord may connect to a properly rated power distribution unit, individual
AC power receptacles, or to a UPS. A rack-mounted UPS is recommended.
To connect the power cords:
1 Ensure that the circuit breakers at the AC load center are OFF.
2 Connect the media gateway to the UPS or to an nonswitched or always on electrical
outlet.