1 Connect one end of the conductor to a telephone cable building entrance protector
ground that is connected to an approved ground.
2 Route the conductor next to the exposed telephone cables being protected until it reaches
the crossconnect nearest to the telephone system.
3 Position the nonexposed telephone cables at least 12 inches (30.5 centimeters) away
from exposed telephone cables whenever possible.
4 Terminate the other end to the single-point ground block provided for the telephone
system.
Connect the Power Cords
!
WARNING:
The AC power cord may connect to a properly rated power distribution unit, individual
AC power receptacles, or to a UPS. A rack-mounted UPS is recommended.
To connect the power cords:
1 Ensure that the circuit breakers at the AC load center are OFF.
2 Connect the media gateway to the UPS or to an “nonswitched” or “always on” electrical
outlet.