Technical Data
Instruction handbook b maXX BM3000, BM3200, BM3300
Document no. 5.11018.11
29
of 218
3
3.3.5 Required environmental conditions
1)
For an operation in an environment of category C2 according to IEC 61800-3:2012 additional measures may be required.
In this case the system manufacturer/operator must provide evidence, that these additional measures are effective and that the limit
values specified in IEC 61800-3 of category C2 are complied with.
2)
See correction factors at modified environment conditions, ZEnvironmental temperature– on page 31.
3)
See correction factors at modified environment conditions, ZInstallation altitude– on page 30.
BM3000 BM3200, BM3300
Transportation temperature range -25 °C to +70 °C
Transportation climate classification
EN 60721-3-2
2 K 3
Storage temperature range -25 °C to +55 °C
Storage climate classification
EN 60721-3-1
1 K 4
Operation environment Industrial supply network
1)
Operation temperature range min. 5 °C to max. 40 °C min. 5 °C to max. 55 °C
(with derating above 40 °C)
2)
Operation climate classification
EN 60721-3-3
3 K 3
Installation altitude up to 2000 m altitude
(with derating above 1000 m)
3)
Humidity (operation)
EN 60721-3-3
relative humidity: 5 % to 85 % non-condensing
and
absolute humidity: 1 g/m
3
to 25 g/m
3
Ionizing and non-ionizing radiation < measurable range
Vibration, shock and repetitive shock
EN 61800-5-1, section 5.2.6.4 vibration test
max. 0.5 g operating (1 g tested)
Pollution degree
EN 61800-5-1, table 6, tab. 2
2
NOTICE!
Normally, only non-conductive pollution occurs. Any conductive pollution, if for a
short-term or permanently, is forbidden and can cause the destruction of the device.
The customer is responsible for destructions, which are caused by conductive mate-
rials.