Electrical data
Instruction handbook b maXX BM3000, BM3200, BM3300
Document no. 5.11018.11 Baumüller Nürnberg GmbH
42
of 218
3.4
3.4.5 Electrical data BM3XXX-XE, 230 V
a)
with internal ballast resistor BM3X02-XEXX-XXXXX-B-XXXXX-
b)
without internal ballast resistor BM3X02-XEXX-XXXXX-E-XXXXX-
BM3X02
1-phase/
1 x 230 V
BM3X03
1-phase/
1 x 230 V
BM3X04
1-phase/
1 x 230 V
BM3X12
1-phase/
1 x 230 V
BM3X13
1-phase/
1 x 230 V
Input rated power output
1)
0.8 kVA 1.1 kVA 1.9 kVA
Input rated current (I
eff
)
1) 2) 3)
3.5 A 4.5 A 5.6 A
Distortion factor of the input current (THD
I
)
1)
95 %
Input peak current (I
eff
)
1) 2) 3)
5.6 A
DC-link voltage power supply-dependent/rating 300 V
DC
DC-link capacitance (internal), external not permitted 235 µF
DC-link discharge time (internal DC-link capacitance) ca. 450 s
Output voltage
(U
AC
)
1) 4)
0 ... 230 V
Output frequency at 4 kHz
5) 6)
0 ... 450 Hz
Maximum output power 0.6 kW 1.08 kW 1.5 kW
10)
Output rated current
(I
AC
)
1)4)7)8)9)
at 2 kHz
5)
1.5 A 2.7 A 5 A 6.5 A 10 A
Output rated current (I
AC
)
1)4)7)8)9)
at 4 kHz
5)
1.5 A 2.7 A 5 A 6.5 A 10 A
Output rated current
(I
AC
)
1)4)7)8)9)
at 8 kHz
5)
1.1 A 1.9 A 3.5 A 4.8 A 7 A
Output rated current (I
AC
)
1)4)7)8)9)
at 16 kHz
5)
0.8 A 1.3 A 2.5 A 3.4 A 5 A
Output peak current (I
AC
)
1)4)7)8)9)
at 2 kHz
5)
6 A 11 A 15 A 20 A
Output peak current
(I
AC
)
1)4)7)8)9)
at 4 kHz
5)
6 A 11 A 15 A 20 A
Output peak current (I
AC
)
1)4)7)8)9)
at 8 kHz
5)
4.2 A 7.7 A 10.5 A 14 A
Output peak current
(I
AC
)
1)4)7)8)9)
at 16 kHz
5)
3 A 5.4 A 7.4 A 10 A
Max. peak current time 60 s 30 s 10 s
Ballast start-up voltage 785 V
Ballast peak power, internal ballast resistor
a)
1200 W for max. 150 ms
Average ballast power, internal ballast resistor
a)
100 W
Permitted ballast current (Î), external ballast resistor
b)
max. 7.0 A max. 12.8 A
Ballast resistor, external ballast resistor
b)
111 61
Ballast peak power, external ballast resistor
b)
5.5 kW 10 kW
Permitted continuous power of external ballast resistor
b)
2.5 kW 5 kW
Switch on ready-to-operate after 4 s
Max. upload time 0.5 s
Power loss referring to power connection 50 W
Power loss referring to control voltage max. 30 W
Cooling air requirement 11 m
3
/h