Maintenance
Instruction handbook b maXX BM3000, BM3200, BM3300
Document no. 5.11018.11
167
of 218
9
9.3.1 Periodic maintenance
m environmental condition
Check points Methods and criteria Inspection intervals
Daily Semi-
an
nu-
ally
Annu-
ally
Check environmental temperature, humidity and
vibr
ations.
Check, whether dust, oil or water drops are visible.
Visual inspection and measurement of the environmen-
tal conditions, comparison with standard values.
O
Check, whether there are hazardous objects in the
vi
cinity.
Visual inspection O
m Voltage
Check points Methods and criteria Inspection intervals
Daily Semi-
ann
u-
ally
Annu-
ally
Check the voltage of the power supply network
and the
control circuits
Measurement and comparison with standard values. O
DANGER!
Risk of fatal injury from electrical current!
Stored electric charge.
Discharge time of the modular system = discharge time of the device with the longest
DC link discharge time in the modular system.
Refer to Z Electrical Data .
Therefore:
m Do not touch before taking into account the discharge time of the capacitors and
electrically live parts.
m Heed corresponding notes on the equipment.
m If additional capacitors are connected to the intermediate circuit, the intermediate
circuit discharge can take a much longer time. In this case, the necessary waiting
period must itself be determined or a measurement made as to whether the equip-
ment is de-energized. This discharge time must be posted, together with an IEC
60417-5036 (2002-10) warning symbol, on a clearly visible location of the control
cabinet.