Shielding plan
Instruction handbook b maXX BM3000, BM3200, BM3300
Document no. 5.11018.11 Baumüller Nürnberg GmbH
92
of 218
7.8
7.8.2.2 Connecting the shield
It is recommended to connect the shielding according following figure, see also ZAcces-
sories kit shielding BM3200, BM3300– on page 197.
1 pr
epare motor cable according figure
2 rem
ove the motor temperature cable’s shield from the cable
3 wra
p motor temperature cable around motor cable at least 1 turn, form no loop.
RIGHT
WRONG
Shield
motor cable
Motor cable
Motor temperature
cable
Shield
motor temperature
cable
Figure 34: Wrap shield motor temperature cable around motor cable