Instruction handbook b maXX BM3000, BM3200, BM3300
Document no. 5.11018.11 Baumüller Nürnberg GmbH
56
of 218
4.3
ZFusesfrom page 191
n Devices are suitable for use on a circuit capable of deliver-
ing not more than 5000 rms symmetrical amperes,480Y/277 V
AC
maximum
m when protected by J Class Fuses rated min. 480 V
AC
, max. 15 A
or
m when protected by a circuit breaker rated min. 480/277 V,
max. 20 A.
n Integral solid state short circuit protection does not provide
branch circuit protection. Branch circuit protection must be
provided in accordance with the Manufacturer Instructions,
National Electrical Code and any additional local codes.