EasyManua.ls Logo

Chroma 11210 - 11210 And A112102 Setup

Chroma 11210
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A112102 PD Test Checking Kit (Option)
8-7
8.3.1 11210 and A112102 Setup
Assuming the test voltage is 500V when not connected to DUT, the expected PD simulation
signal level is about 30. From Table 8-2, we know the capacitance is #5 as the VPD and CPD
level is about 27~33.
8.3.1.1 Setting Test Parameters
For the IR/LC measurement related settings and parameters, please see section 5.3.1, 5.3.2
and 5.3.3. See section 6.4 and 6.4.2 for setting PD Compare parameters.
Test Parameter
Parameter
Default Value
11210
Insulation Test
Test Voltage
500V
Charge Current
1mA
LC Range
20mA
Trigger Mode
Manual
Integration Time
1PLC
Charge Time
2000ms
Dwell Time
2000ms
Test Time
2000ms
PD Compare
VPD Level
1
VPD Level
1
8.3.1.2 Setting A112102 Parameters
Test Parameter
Parameter
Default Value
A112102
PD Simulation
Test
Voltage Trigger
20V
PD Interval
0.4s
PD Capacitance
#5
Partial Discharge
Multiple
Setting Voltage Trigger:
Since the test voltage is 500V, the A112102 will send out PD simulation signals as long as the
voltage trigger is set to less than the test voltage (500V). In this example, the trigger is set to
20V.
Setting PD Capacitance:
For 500V test voltage, select #5 as the mapping capacitance tha has 27~33 of occurrences.
Setting PD Interval:
The times of PD simulation signal is related to the PD Interval. VPD is the PD signals occurred
within Charge Time while CPD is the PD signal occurred in Dwell Time and Test Time. The PD
simulation signal occurrence times can be calculated following this rule.
VPD times (Charge Time)/ PD Interval +1
CPD times (Dwell Time+Test Time)/ PD Interval

Table of Contents

Related product manuals